• Rated Voltage (Un): 230 / 400V AC (3 ~)
• Operating voltage: 161/279 - 300 / 520V AC (3 ~)
• Insulation capacity:
- AC voltage: 2KV for 1 minute
- Voltage pulse load capacity: 6KV - 1.2µS
• Rated current (Ib): 1.5A
• Maximum current (Imax): 6A
• Operating current range: 0.4% Ib-Imax
• Installation power (S1): <0.01VA (per phase, the AV input is short-circuited with a ferrite ring to which the power meter itself is connected). stay within and measure accurately:
R = (2 * ρ * L) / A
Where ρ: specific resistance of the copper wire, A: cross section of the copper wire, l: length of the copper wire.
S2 = I2 * R
Where I: Secondary current of current transformer (5A)
Circuit load: S = S1 + S2, which shows that the power absorbed by the meter (S1) is negligible.
According to the standard MSZ EN60044-1, the rated current of the current converter (Snévl) shall be adapted to the load of the secondary circuit, the value between 25-100% of the rated power shall be: 0.25 * Snévl ≤ S ≤ Snévl
• Overcurrent Hold: 30 x Imax for up to 0.01s
• Output indicator value (LED): 1600imp / kWh
• Pulse output value: 1600imp / kWh
• Power Feedback (LED A, B&C): Device A / B / C Power
• Power consumption feedback measurement: flash (PULSE & LED)
• Adjustable current range 27 different types
• International Standard: IEC 62053-21
• Accuracy class: 1
• IP protection: IP51 (with protective cover)
• Choose from 27 range values (“5: 5” to “7500: 5”)
• It is recommended that an external fuse or thermal cut-out be connected to the supply line to protect the device against overcurrent.
• Mounted on 35mm DIN rail.
• If environmental effects warrant it, it is recommended that the device be provided with surge protection devices.
• After wiring, the device can be sealed.